Modular Humidity / Temperature Sensor

Open Link in Lightbox
  • Humidity
  • Temperature

EE212

The EE212 humidity (RH) and temperature (T) sensor with interchangeable sensing module is optimized for demanding climate control applications in most various industries.

  • EE212 modular humidity and temperature sensor for wall mounting with display and digital interface

  • EE212 modular humidity and temperature sensor for wall mounting with display

  • EE212 modular humidity and temperature sensor for duct mounting

    Versatility
    The EE212 is available for wall or duct mount as well as an outdoor version. It features two analogue outputs as well as a BACnet MS/TP or Modbus RTU interface and optional graphic display. Besides the accurate RH and T measurement, the sensor calculates various humidity related parameters such as dew point temperature, absolute humidity and mixing ratio.

    Outstanding Reliability
    The proprietary coating of the E+E sensing element, the wide choice of filter caps and the IP65 / NEMA 4 enclosure ensure excellent long-term performance of EE212 even under challenging working conditions. Easy on-site replacement of the sensing module minimizes the down-time for maintenance purposes in heavily polluted or aggressive environment.

    Interchangeable, Robust Sensing Module
    The injection-moulded sensing module inside the sensing head is mechanically highly stable, easy to handle and requires no tools for replacement. The electronics inside the module is encapsulated and therefore best protected against condensation.

    User Configurable and Adjustable
    The free EE-PCS Product Configuration Software and an optional adapter cable facilitate the configuration and adjustment of the EE212. The configuration includes the measurands assignment (two on the outputs and up to three on the display), the output scale and the display settings.

    For the use of this service, prior consent to the processing of your data and in particular to the setting of cookies is necessary. You can consent to the processing and setting of cookies here. Without your consent, your data will not be processed in connection with this service and no cookies will be set. You can revoke your consent at any time. For more information on cookies and the processing of your data in connection with this content and a way to revoke your consent, please see our privacy policy.

    Key Features

    • Interchangeable RH/T sensing module
    • RH/T sensing element with proprietary coating and sealed solder pads
    • Very robust sensing head
    • BACnet MS/TP or Modbus RTU
    • High accuracy
    • Calculation of various humidity related parameters
    • Configurable display with backlight
    • User configurable and adjustable by the EE-PCS
    • IP65/NEMA 4 enclosure
    • Easy mounting and handling

    Technical data

    Measuring range Humdity
    0...100% RH


    Accuracy Humdity
    23 °C ±(1.5+0.005*mv)% RH
    -15...60 °C ±(1.8+0.007*mv)% RH
    -40...-15 °C additional uncertainty ±0.125 %RH/°C
    Measuring range Temperature
    -40...60 °C (-40...160 °F)
    Accuracy Temperature
    ±0.3 °C (0.54°F)
    Analogue outputs
    0-5/10 V or 0/4-20 mA
    Digital output
    BACnet MS/TP or Modbus RTU
    Supply
    24V AC/DC

    Calibrating your limits

    Your products and services can only be as precise as the tools you use to measure them. With more than 20 years of experience, the calibration team of E+E Elektronik focuses on providing a reliable service without any unnecessary delays or bias.

    Discover the value of working with an expert in calibration that prioritizes

    • accuracy,
    • fastness and
    • reliability

    Learn more